2012 ©
             Publication
Journal Publication
Title of Article Effect of transverse rib on heat transfer between circulating fluidized bed and membrane fins of water wall membrane tubes 
Date of Acceptance 19 March 2018 
Journal
     Title of Journal Powder Technology 
     Standard ISI 
     Institute of Journal elsevier 
     ISBN/ISSN
     Volume 2018 
     Issue 332 
     Month June
     Year of Publication 2018 
     Page 178-187 
     Abstract Overall heat transfer between circulating fluidized beds (CFB) and the ribbed membrane fins of awaterwall tube was investigated experimentally in a cold model circulating fluidized bed riser. The riser had a cross sectional area of 0.1 × 0.2m2 and the height fromthe distributor plate to the riser exitwas 3.9 m. Three isosceles triangular cross section prisms having a height to base width ratio (e/B) of 0.54 corresponding to the height to riser diameter ratios (e/D) of 0.019, 0.038 and 0.06, respectively were used as ribs. The ribs were installed transversely on the fins with three rib spacings (S) of 0.4 m, 0.5 mand 0.6 m. Local sand having an average diameter of 315 μm was used as the bed material. It was found that the heat transfer coefficients and the cluster solid fractions of the ribbed membrane fins were higher than those of the membrane fin, and varied with the rib spacing and the rib height to diameter ratio in the same manner. In addition, cluster contact time of the ribbed membrane fins was shorter than that for the membrane fin without ribs. 
     Keyword CFB, Bed to wall heat transfer, Particle convection, Heat transfer enhancement, Membrane water wall tube 
Author
557040041-1 Mr. JIRAROCH SOMJUN [Main Author]
Engineering Doctoral Degree

Reviewing Status มีผู้ประเมินอิสระ 
Status ได้รับการตอบรับให้ตีพิมพ์ 
Level of Publication นานาชาติ 
citation true 
Part of thesis true 
Attach file
Citation 0